Utah Code 15A-3-307. Amendments to Chapter 7 of IPC
Current as of: 2023 | Check for updates
|
Other versions
15A-3-307. Amendments to Chapter 7 of IPC.
(1) | IPC, Section 701.2, is deleted and replaced with the following: “701.2 Sewer required. Every building in which plumbing fixtures are installed and all premises having drainage piping shall be connected to a public sewer where the sewer is accessible and is within 300 feet of the property line in accordance with Utah Code, Section 10-8-38; or an approved private sewage disposal system in accordance with Utah Administrative Code, Rule R317-4, as administered by the Department of Environmental Quality, Division of Water Quality.” |
(a) | 4; and |
(b) | Chapter 5, State Fire Code Act. See Utah Code 15A-1-102 |
(2) | A new IPC Section 701.8 is added as follows: “701.8 Drainage piping in food service areas. Exposed soil or waste piping shall not be installed above any working, storage, or eating surfaces in food service establishments.” |
(3) | In IPC, Section 712.3.3.1, the following words are added after the word “PE”: “stainless steel, cast iron, galvanized steel, brass,”. |
Amended by Chapter 20, 2019 General Session