Florida Regulations 25-30.262: Meter Accuracy Requirements
Current as of: 2024 | Check for updates
|
Other versions
Each utility shall employ water meters which register within the accuracy limits set forth in this chart:
Accuracy limits in percentages
Maximum
Intermediate
Minimum Rate
Meter Type
Rate
Rate
New
Repaired
Displacement
98.5-101.5
98.5-101.5
95-101.5
90-101.5
Current
97-102
None
95-102
90-102
Compound*
97-103
97-103
95-103
90-103
*The minimum required accuracy for compound meters at any rate within the “”changeover”” range of flows shall be 85%.
Rulemaking Authority 350.127(2), 367.121 FS. Law Implemented 367.121(1)(a), 367.122(1) FS. History-New 9-12-74, Formerly 25-10.92, 25-10.092, Amended 11-10-86.