Circuit breakers providing short circuit protection for trailing cables shall be set so as not to exceed the maximum allowable instantaneous settings specified in this section; however, higher settings may be permitted by an authorized representative of the Secretary when he has determined that special applications are justified:

Conductor size AWG or MGMMaximum allowable circuit breaker instantaneous setting (amperes)
1450
1275
10150
8200
6300
4500
3600
2800
11,000
1/01,250
2/01,500
3/02,000
4/02,500
2502,500
3002,500
3502,500
4002,500
4502,500
5002,500